Flammable Gases : Handling Of Dangerous Substances.

Flammable Gases : Handling Of Dangerous Substances. 

When dealing with flammable gases, it's crucial to understand the acceptable frequency rate of explosive atmospheres to ensure safety. Here's a breakdown:

Hazardous Area Classification

  • Zone 0: Areas where an explosive gas atmosphere is present continuously or for long periods (>1000 hours/year).
  • Zone 1: Areas where an explosive gas atmosphere is likely to occur in normal operation (10-1000 hours/year).
  • Zone 2: Areas where an explosive gas atmosphere is not likely to occur in normal operation and, if it occurs, will only exist for a short time (<10 hours/year).

Gas Detection and Monitoring

  • Alarm Activation: Alarms should be activated when the vapor concentration reaches 30% of the Lower Flammable Limit (LFL) in air.
  • Monitoring Intervals: Gas detection equipment should monitor from each sampling head location sequentially at intervals not exceeding 30 minutes.

Ventilation Requirements

  • Minimum Ventilation: 1 cfm/ft² (20 m³/h·m²) to prevent accumulation of flammable gases.
  • Recommended Ventilation: 2 cfm/ft² (40 m³/h·m²) or 12 air changes per hour, with half the air supplied and exhausted near the ceiling and half near the floor.

Safety Measures

  • Gas Detectors: Should be constructed to a Zone 1 standard and set to operate at 25% of the LFL of a gas or vapor.
  • Protective Devices: Linked to detection systems, including alarms, warning lights, reaction quenching systems, isolation systems, fire retardant systems, plant shutdown systems, and trip devices